Program blocks
5.10 Switch and relay blocks
RTU303xC
320
Operating Instructions, 06/2019, C79000-G8976-C382-06
Parameters
Parameters
Tag type / range of
values
Description
Input parameters
En
Enable parameter, see section Often used parame-
Trigger
True / False
Digital input / output /
bit memory
STATUS_ERROR
When there is an edge change 0
→
1 a new pulse
sequence begins.
With the setting "True", the pulse sequence set in
the parameters runs precisely once after the RTU
starts up or after a new configuration has been
adopted.
With the setting "False" the output is never set.
Function parameters
Pulse duration (ms)
100 .. 999999999
Pulse duration in milliseconds
Interpulse period (ms) 0 .. 999999999
Pause between two pulses in milliseconds
If the number of pulses is > 1 or the Start value
"Pause" is selected, the Interpulse period must be ≥
100 ms.
Cycles
1 .. 999999999
Specifies the number of pause/pulse cycles (pulse
sequence).
Start value
•
Pulse
•
Pause
•
With "Pulse" the pulse sequence starts with a
"1" at the output.
•
With "Pause" the pulse sequence starts with a
"0" at the output.
End
•
Trigger
•
Time
•
With "Trigger", the pulse sequence ends as
soon as the "Trigger" input changes to 0 or the
configured number of cycles is reached.
•
With "Time" the pulse sequence ends when it
has run completely.
Output parameters
Output
Digital output / bit
memory
Tag in which the value calculated by the block is
output.
Содержание Simatic RTU3030C
Страница 248: ...Configuration WBM 4 24 Tag tables RTU303xC 248 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 350: ...Dimension drawings RTU303xC 350 Operating Instructions 06 2019 C79000 G8976 C382 06 Figure B 2 Side view ...
Страница 376: ...Accessories C 7 Overvoltage protection modules RTU303xC 376 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 390: ...Documentation references E 10 10 RTU303xC 390 Operating Instructions 06 2019 C79000 G8976 C382 06 ...