Program blocks
5.10 Switch and relay blocks
RTU303xC
318
Operating Instructions, 06/2019, C79000-G8976-C382-06
Tr
S
R
Q
Trigger
Set
Reset
Output
Figure 5-12 Switching diagram of a block "Current impulse relay", RS/SR priority = SR
Parameters
Parameters
Tag type / range of
values
Description
Input parameters
En
Enable parameter, see section Often used parameters
(Page 252).
Set
True / False
Digital input / output /
bit memory
STATUS_ERROR
Sets the output to 1 on a positive edge (0
→
1).
With the setting "True", the output remains permanently
at 1. Resetting via the "Reset" input is then only possible
when "RS/SR priority" = RS.
With the setting "Unused" or "False", the output is only
controlled by the inputs "Reset" and "Trigger".
Reset
True / False
Digital input / output /
bit memory
STATUS_ERROR
On a positive edge (0
→
1) resets the output to 0 when
"Set" = 0 or when the "RS/SR priority" = RS.
With the setting "True" "Set" is permanently reset and the
output remains permanently set to 0.
With the setting "unused" or "False", the "Set" input is not
reset.
With the setting "Unused" or "False", the output is only
controlled by the inputs "Reset" and "Trigger".
Trigger
True / False
Digital input / output /
bit memory
STATUS_ERROR
The edge change 0
→
1 of "Trigger" has the following
effect:
•
When "Set" and "Reset" = 0, the output is set to 1.
•
When "Set" and "Reset" = 1 and the "RS/SR priority"
= SR, the output is set to 1.
•
When "Set" and "Reset" = 1 and the "RS/SR priority"
= RS, the output is set to 0.
•
If only "Set" = 1, the output remains at 1.
•
If only "Reset" = 1, the output remains at 0.
The edge change 1
→
0 of "Trigger" has no effect:
Содержание Simatic RTU3030C
Страница 248: ...Configuration WBM 4 24 Tag tables RTU303xC 248 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 350: ...Dimension drawings RTU303xC 350 Operating Instructions 06 2019 C79000 G8976 C382 06 Figure B 2 Side view ...
Страница 376: ...Accessories C 7 Overvoltage protection modules RTU303xC 376 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 390: ...Documentation references E 10 10 RTU303xC 390 Operating Instructions 06 2019 C79000 G8976 C382 06 ...