Configuration (WBM)
4.12 Maintenance
RTU303xC
Operating Instructions, 06/2019, C79000-G8976-C382-06
123
Save configuration
With this function the current configuration data of the RTU is saved in a configuration file.
●
Save on SD card
Saves the current configuration file under the name "user.cfg" on the SD card.
●
Compress and encrypt file (optional)
If you enable the option, the configuration file is saved and encrypted compressed as a
ZIP archive.
●
Password for optional encryption
Input box for the password for encryption of the configuration file
The following requirements apply to the password to be entered:
–
Length: At least 1 character, maximum 16 characters.
–
Permitted characters
Digits, lowercase letters, uppercase letters and special characters from the ASCII
character set 0x20 .. 0x7e
See also section Permitted characters and parameter lengths (Page 95).
–
Required characters: Free combination of the permitted characters
●
Save to PC
Saves the current configuration file under the name "user.cfg" on the configuration PC.
Names of the configuration files
You can save different configuration files on the SD card.
Automatic saving in the configuration file "default.cfg"
When using an SD card if the configuration data of the RTU is automatically stored in the file
"default.cfg".
When changed configuration data is adopted the file "default.cfg" is automatically updated on
the SD card.
Manual saving in the configuration file "user.cfg"
When you save manually using the WBM, the configuration data is stored on the SD card in
a file with the default name "user.cfg".
In addition to this, with each change to the configuration data the file "default.cfg" is
automatically updated.
Startup of the RTU with configuration files
If you store different configuration files on an SD card and plug this into an RTU, the RTU
always runs with the internal configuration data.
If an SD card with the file "default.cfg" is inserted in a brand-new RTU or an RTU reset to the
factory settings, the RTU always starts with the file "default.cfg".
Содержание Simatic RTU3030C
Страница 248: ...Configuration WBM 4 24 Tag tables RTU303xC 248 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 350: ...Dimension drawings RTU303xC 350 Operating Instructions 06 2019 C79000 G8976 C382 06 Figure B 2 Side view ...
Страница 376: ...Accessories C 7 Overvoltage protection modules RTU303xC 376 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 390: ...Documentation references E 10 10 RTU303xC 390 Operating Instructions 06 2019 C79000 G8976 C382 06 ...