Configuration (WBM)
4.18 Operating mode
RTU303xC
Operating Instructions, 06/2019, C79000-G8976-C382-06
169
4.18.2
Logging
You will find the naming conventions of the log files in the section SD card (Page 113).
●
Active
Selecting the check box turns on logging. A further requirement is a plugged in SD card.
●
Log file creation
Here you specify the cycle in which new log files are created: Daily, weekly, monthly
●
Response when insufficient memory space on SD card
Here you specify the response if there is no longer enough memory space on the SD
card for new log files:
–
Delete older log files
The process data continues to be acquired. When the SD card is full, with the creation
of new log files the oldest log files are successively deleted (FIFO principle).
–
Stop logging
Already stored process data is retained. When the SD card is full, saving new process
data is suspended until data is deleted manually from the SD card.
●
Separator
Here, you specify the separate between the individual blocks of data in the log file:
Comma, colon or semicolon
●
Log file name prefix
Here you can enter a name prefix with a maximum of three characters that is placed at
the beginning of the file name of the log file.
●
Maximum number of Log files
Here you specify the maximum number of log files that will be saved on the SD card:
Max. 999999
Содержание Simatic RTU3030C
Страница 248: ...Configuration WBM 4 24 Tag tables RTU303xC 248 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 350: ...Dimension drawings RTU303xC 350 Operating Instructions 06 2019 C79000 G8976 C382 06 Figure B 2 Side view ...
Страница 376: ...Accessories C 7 Overvoltage protection modules RTU303xC 376 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 390: ...Documentation references E 10 10 RTU303xC 390 Operating Instructions 06 2019 C79000 G8976 C382 06 ...