Program blocks
5.6 Blocks for time functions
RTU303xC
Operating Instructions, 06/2019, C79000-G8976-C382-06
267
Tr
Ton
R
Q
Trigger
On delay
Reset
Output
Figure 5-5
Circuit diagram of a block. "Retentive on delay"
Parameters
Parameters
Range of values
Description
Input parameters
En
Enable parameter, see section Often used parameters
(Page 252).
Trigger
•
True / False
•
Digital input /
output / bit
memory
•
STATUS_ERROR
When there is an edge change 0
→
1 the time of On
delay is started.
With the setting "True" the trigger is always active.
With the setting "False" the block is never processed.
Reset
•
True / False
•
Digital input /
output / bit
memory
•
STATUS_ERROR
When there is an edge change 0
→
1 at the "Reset" input
after the On delay ( = 1) has elapsed the output is reset
to 0.
With the setting "True" the input is always active and the
output is set to 0 immediately. The function is therefore
actually turned off.
With the setting "False" the input is never active.
Function parameters
On delay (ms)
100 .. 999999999
On delay in milliseconds
After the time of the On delay has elapsed, the output is
set to 1.
Output parameters
Output
•
Digital output / bit
memory
Tag in which the value calculated by the block is output.
Содержание Simatic RTU3030C
Страница 248: ...Configuration WBM 4 24 Tag tables RTU303xC 248 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 350: ...Dimension drawings RTU303xC 350 Operating Instructions 06 2019 C79000 G8976 C382 06 Figure B 2 Side view ...
Страница 376: ...Accessories C 7 Overvoltage protection modules RTU303xC 376 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 390: ...Documentation references E 10 10 RTU303xC 390 Operating Instructions 06 2019 C79000 G8976 C382 06 ...