Operating Instructions, 06/2019, C79000-G8976-C382-06
Parameters
Tag type / range of
values
Description
Trigger
True / False
•
Digital input / out-
put / bit memory
•
STATUS_ERROR
If there is an edge change 0 → 1 the outp
ut is set to
1.
When there is an edge change 1
→
0 the Off delay
is started.
After the Off delay has elapsed, the output is set to
0.
With the setting "True" the output is always active.
With the setting "False" the output is never set.
If the "Trigger" input is switched on and off again
while T
a
is running, T
a
is reset
Reset
True / False
•
Digital input / out-
put / bit memory
STATUS_ERROR
When there is an edge change 0
→
1 Off delay is
stopped and the output is set to 0. As long as "Re-
set" is set to 1, the value of "Trigger" is ignored.
When there is an edge change 1
→
0 the block can
be processed again.
With the setting "True" the input is always active
and the block is essentially turned off .
With the setting "False" the Off delay is never reset.
Function parameters
Off delay (ms)
100 .. 999999999
Delay in milliseconds
Prewarning (ms)
0 .. 999999999
Time of the Prewarning in milliseconds
The sum of Prewarning and Interruption must be
lower than the Off delay.
Interruption (ms)
0 .. 999999999
Duration of the interruption in milliseconds
The "Interruption" may not exceed the "Prewarn-
ing".
An interruption of 0 is only allowed when:
•
the "Warning" output is connected
or
•
Pre-warning = 0 and the "Warning" output is not
connected.
Output parameters
Output
•
Digital output / bit
memory
Tag in which the value calculated by the block is
output.
Warning
•
Digital output / bit
memory
The optional output is set to 1 at the start of the
prewarning.
Along with "Output" changes to 0.
Содержание Simatic RTU3030C
Страница 248: ...Configuration WBM 4 24 Tag tables RTU303xC 248 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 350: ...Dimension drawings RTU303xC 350 Operating Instructions 06 2019 C79000 G8976 C382 06 Figure B 2 Side view ...
Страница 376: ...Accessories C 7 Overvoltage protection modules RTU303xC 376 Operating Instructions 06 2019 C79000 G8976 C382 06 ...
Страница 390: ...Documentation references E 10 10 RTU303xC 390 Operating Instructions 06 2019 C79000 G8976 C382 06 ...