Siemens Building Technologies
Basic Documentation RVA63.242, RVA53.242
CE1P2373E
Landis & Staefa Division
Description of heating engineer settings
26.03.2001
4.24 Display of flow temperature setpoint HK1
(TRw)
Displays the current flow temperature setpoint of the heating circuit.
When selecting this operating line, the current flow temperature setpoint of the
controller’s internal heating circuit is displayed.
Display
Unit
0...140
°C
The value displayed corresponds to the flow temperature of the heating circuit that is
required for satisfying the demand for heat.
The display shows “---“ in the following situations:
−
No heating circuit available
−
ECO function active (summer / winter changeover, automatic 24-hour heating limit)
−
Quick setback active
−
Room temperature limitation active
4.25 Display of flow temperature setpoint HK2
(TVw)
Function and effect of this setting are basically the same as with setting 75 described
above.
Display
Unit
0...140
°C
4.26 Floor curing data HK1
Information about the current state
of floor curing.
The floor curing function has a fixed profile according to which the rooms are heated to
allow curing. The current values of the floor curing function are displayed here. The
function itself is activated under setting 116.
Display
Unit
- -
- -
(Inactive)
0...32
0...95
Day TVw