Handling
26.03.2001
2.5 Parameter settings for the heating engineer
Configuration and parameter settings to be made by the heating engineer.
Buttons
Explanation
Line
1
Press one of the line selection buttons UP/DOWN.
This will take you directly to the programming mode
"End-user”.
2
Press both line selection buttons for at least 3 seconds.
This will take you directly to the programming mode
"Heating engineer”.
3
Press the line selection buttons to select the required
line.
The parameter list on the next 2 pages contains all
available lines.
• • •
4
Press the + or - button to set the required value.
The setting will be stored as soon as you leave the
programming mode or change to another line.
The parameter list on the next 2 pages contains all
settings that can be made.
5
By pressing any of the operating mode buttons you
leave the programming mode "Heating engineer”.
è
Note:
If no button is pressed for about 8 minutes, the
controller will automatically return to the operating
mode selected last.
Continuous
display
Description
Setting