162/218
Siemens Building Technologies
Basic Documentation RVA63.242, RVA53.242
CE1P2373E
Landis & Staefa Division
Description of OEM settings
26.03.2001
5.15 Switching differential of damper actuator
Setting the switching differential for 2-position control of the damper actuator.
Adjustable switching differential for burner control.
Setting range
Unit
Factory setting
0...20
°C (K)
2
The setting changes the switching differential of air damper control.
Entry:
Increase:
Switching differential becomes wider.
Fewer on / off pulses and longer intervals between full load and basic
load.
Decrease:
Switching differential becomes smaller.
More on / off pulses and shorter intervals between full load and basic
load.
°C
2373Z62
Auf
Z u
w
SD
TKx
w
Setpoint
SD
Switching differential damper actuator
Switch-on point
Switch-off point
TKx
Actual value of boiler temperature
Benefit
Description
Setting
Effect
Switching differential