98/218
Siemens Building Technologies
Basic Documentation RVA63.242, RVA53.242
CE1P2373E
Landis & Staefa Division
Description of heating engineer settings
26.03.2001
4.36 Switching differential of the room temperature
(SDR)
Temperature control with pump heating circuits.
Prevents overtemperatures in the rooms in the case of a pump heating circuit.
Serves as a room temperature limitation with pump heating circuits
Setting range
Unit
Factory setting
– . – / 0.5...4.0
°C
– . –
The switching differential for two-position control will be changed.
Entry:
– . –
Switching differential is inactive
•
The pump always remains activated
Decrease:
Switching differential will become smaller
•
Pumps are switched on and off
more often
•
Room temperature varies within a
narrower
band
Increase:
Switching differential will become greater
•
Pumps are switched on and off
less often
•
Room temperature varies within a
wider
band
The room temperature sensor must be active
•
This function only acts in automatic mode
•
The display will show "ECO“
With pump heating circuits, the amount of heat supplied is controlled by switching the
pumps on and off. This is accomplished with 2-position control by means of the room
temperature's switching differential.
Functioning:
OFF
ON
P
°C
TRx
TRw+SDR
2371D02
TRw
t
Legend
TRx
Actual value of the room
temperature
TRw
Room temperature setpoint
SDR
Switching differential of the
room temperature
P
Pump
ON
Switch-on point
OFF
Switch-off point
t
Time
Pump ON
TRw
Pump OFF
TRw =TRw + SDR
°C
2373Z14
O N
OFF
w
TRx
Actual value of the room
temperature
TRw
Room temperature setpoint
SDR
Switching differential of
room temperature
w
Setpoint
102
Switching differential of the
room temperature
Switch-on point
Switch-off point
Benefits
Description
Setting
Effect
Note
Room temperature
control
Switching differential