214/218
Siemens Building Technologies
Basic Documentation RVA63.242, RVA53.242
CE1P2373E
Landis & Staefa Division
Technical data
26.03.2001
9
Technical data
Power supply
Nominal voltage
Nominal frequency
Power consumption
AC 230 V (±10 %)
50 Hz (±6 %)
max. 7 VA
Requirements
Safety class (if adequately mounted)
Degree of protection (if adequately mounted)
Electromagnetic immunity
Electromagnetic emissions
II to EN 60730
IP 40 to EN 60529
EN 50082-2
EN 50081-1
Climatic conditions
Operation
To IEC 721-3-3
Temperature
Class 3K5
0..0.50°C
Storage
To IEC 721-3-1
Temperature
Class 1K3
-25..0.70 °C
Transport
To IEC 721-3-2
Temperature
Class 2K3
-25..0.70 °C
Mechanical conditions:
Operation to IEC 721-3-3
Storage to IEC 721-3-1
Transport to IEC 721-3-2
Class 3M2
Class 1M2
Class 2M2
Mode of operation
To EN 60730 par. 11.4 11.4
1b
Output relays
Voltage range
Nominal current
Switch-on peak
Anschlussabsicherung
AC 24...230 V
5 mA...2 A (cos phi > 0.6)
max. 10 A, max. 1 s
max. 10A
Bus extension
PPS
Cable (telephone wire)
Permissible cable length
2 x 0.5 mm
2
(interchangeable)
50 m
LPB
Cable
Permissible cable length
Node spacing
(2-wire,
not
interchangeable)
max. 1.4 km
500 m (with copper cable 1.5 mm
2
)
Bus loading number (E)
3
Perm. sensor cable lengths
0.6 mm dia.
1.0 mm
2
1.5 mm
2
max. 20 m
max. 80 m
max. 120 m
Inputs
Outside sensor
D.h.w. sensor
Flow sensor
Remote telephone switch, auxiliary switches
(H1, H2), and d.h.w. control thermostat
NTC (QAC31), Ni 1000 (QAC21)
Ni 1000
Ω
at 0 °C (QAZ21)
Ni 1000
Ω
at 0 °C (QAD21)
suitable for low voltage
(gold-plated contacts)
Miscellaneous
Weight of controller
approx. 0.6 kg
Clock reserve
min. 12 h