3.33 Indication of faults
Straightforward checking of plant.
Fault tracing is made easier.
The controller indicates faults that may have occurred in the controller itself or in the
system.
In normal operation, the display shows "Er" if a fault has occurred.
Display
Unit
0...255
–
The first entry in the fault list will automatically be displayed on this line.
By pressing
, it is possible to switch between fault messages.
The controller can store a maximum of 2 fault messages. The faults message will be
cleared only after the cause of the fault has been removed. If additional faults are
present, they will be stored as soon as storage capacity becomes available.
Faults that can occur on the controller:
Display
Description of fault
Blank
No fault
10
Outside sensor
20
Boiler temperature sensor
28
Flue gas temperature sensor
30
Flow temperature sensor
40
Return temperature sensor
50
D.h.w. temperature sensor connected to B3
52
D.h.w. temperature sensor connected to B31
58
D.h.w. thermostat
61
Fault room unit
62
Wrong room unit
70
Buffer storage tank temperature sensor B4
71
Buffer storage tank temperature sensor B41
73
Collector temperature sensor
81
Short-circuit LPB
82
Address collision on LPB (same address several times)
86
Short-circuit PPS
100
2 clock masters present
140
Inadmissible LPB device or segment number
146
Inadmissible plant configuration
150
General BMU fault
162
Fault contact H2
Benefits
Description
Setting
Effect
Note
Fault messages
Device faults