Description of end-user settings
26.03.2001
Maintenance
3.29 Standard times
Straightforward resetting of all time switch programs to their standard values.
The standard time program resets the time settings of all time switch programs. For this
purpose, the controller is supplied with non-volatile factory settings.
The standard time program is activated as soon as the display changes to 1.
Display
Unit
0 / 1
-
In that case, the individual settings will be lost!
The time settings for the time switch programs will be overwritten with standard values.
This applies to the following settings:
•
Switching times of time switch program 1
...
•
Switching times of time switch program 2
...
•
Switching times of time switch program 3 (d.h.w.)
...
Switching point
Setting line
Standard time
Period 1 ON
6
13
20
06 : 00
Period 1 OFF
7
14
21
22 : 00
Period 2 ON
8
15
22
– – : – –
Period 2 OFF
9
16
23
– – : – –
Period 3 ON
10
17
24
– – : – –
Period 3 OFF
11
18
25
– – : – –
Time switch program
1
2
3
Benefit
Description
Setting
Caution
Effect
Standard values