Description of end-user settings
26.03.2001
0 2 4 6 8 10 12 14 16 18 20 22 24 h
Mo
...
So
2373Z11
3.3.1 Temperature adjustment via room unit
Temperature adjustment or readjustment via a room unit is active only when, on the
controller, automatic mode has been selected!
Adjustment made with the controller’s setpoint knob
=
controller's nominal room temperature setpoint
The QAA50 room unit has a knob for readjusting the setpoint in a + / - range. The
readjustment is added to the actual setpoint adjusted with the controller’s setpoint knob.
Adjustment made with the controller’s setpoint knob
+
readjustment made on the room unit (± 3 °C)
=
controller's nominal room temperature setpoint
Adjustment made with the controller’s setpoint knob
20 °C
Adjustment made with the controller’s setpoint knob
+ 2 °C
Resulting setpoint
22 °C
The QAA70 room unit has an absolute setpoint adjustment using a line, which replaces
the setpoint adjusted with the controller’s setpoint knob, provided automatic mode has
been selected on the controller.
In addition, the QAA70 has a knob for readjusting the setpoint in a + / - range. The
readjustment is added to the actual setpoint adjusted with the controller’s setpoint knob.
Setpoint programmed with the room unit
+
readjustment made on the room unit (± 3 °C)
=
controller's nominal room temperature setpoint
Adjustment made with the controller’s setpoint knob
(inactive)
22 °C
Setpoint adjustment on the room unit’s line
19 °C
Adjustment made with the controller’s setpoint knob
+ 2 °C
Resulting setpoint
21 °C
Without room unit
QAA50
Example:
QAA70
Example: