42/218
Siemens Building Technologies
Basic Documentation RVA63.242, RVA53.242
CE1P2373E
Landis & Staefa Division
Description of end-user settings
26.03.2001
3.3 Nominal room temperature setpoint
Straightforward and direct setting of the required nominal room temperature setpoint.
The heating system uses 3 different setpoints that can be adjusted:
The nominal room temperature setpoint described here
The reduced room temperature setpoint (setting on line 27)
The frost protection setpoint of the room temperature (setting on line 28)
The nominal room temperature setpoint is preadjusted with the
setpoint knob. It is located on the controller front for direct
access by the user.
Setting range
Unit
Factory setting
8...26
°C
20
0 2 4 6 8 10 12 14 16 18 20 22 24 26
°C
2373Z10
Room temperature setpoint setting ranges
27
Setting "Reduced room temperature setpoint”
28
Setting "Frost protection setpoint of the room temperature”
When the nominal room temperature setpoint is active, the rooms will be heated
according to the adjustment made with the setpoint knob.
Effect in the various operating modes:
Operating mode
Effect of knob adjustment
Adjustment acts on the heating periods
Adjustment acts continuously
Adjustment has no effect
The adjustment made with the setpoint knob has priority over the reduced room
temperature setpoint entered (line 27). Especially in a situation when the adjustment
made with the knob is lower.
During the heating periods, the nominal room temperature setpoint is maintained. The
heating periods are in accordance with the settings made on lines 6 through 11 and 13
through 18.
Benefit
Description
Setting
Effect of temperature
setting
Note
Example