151/218
Siemens Building Technologies
Basic Documentation RVA63.242, RVA53.242
CE1P2373E
Landis & Staefa Division
Description of OEM settings
26.03.2001
5.4 Minimum limitation of the burner running time
Reduction of burner switching frequency.
Also termed "Burner cycling protection“.
Setting range
Unit
Factory setting
0...10
min
4
Once switched on, burner stage 1 will remain activated for at least the period of time
set here.
As soon as the burner is switched on, the minimum burner running time starts to make
certain the burner will not be switched off before the set minimum time has elapsed.
Each time the burner is switched off, the minimum burner running time will be reset if
not yet elapsed.
If the boiler temperature exceeds the setpoint by the amount of the entire switching
differential, the minimum burner running time will be ignored for safety reasons
0
1
0
50
40
30
1
TK
t
4
12
16
20
0
60
°C
TK
tBRmin
min
TKw
+SDK/2
x
2371D04
TKw
TKw-
SDK/2
8
TKw
+SDK
FZ
BR
BR
Burner
FZ
Release counter
SDK
Switching differential of the boiler
tBRmin
Minimum burner running time
TKw
Boiler temperature setpoint
TKx
Actual value of boiler temperature
Benefit
Note
Setting
Effect
Minimum burner running
time
Restriction