Basic Documentation RVA63.242, RVA53.242
CE1P2373E
Landis & Staefa Division
Description of OEM settings
26.03.2001
5
Description of OEM settings
Heat generating equipment
5.1 Minimum limitation of boiler temperature
(TKmin
OEM
)
Factory-set limitation.
Setting range
Unit
Factory setting
8... Tkmin
°C
40
Tkmin
Minimum limitation of boiler temperature (setting on line 81)
The setting will ensure low limitation of the boiler temperature’s minimum limitation set
on line 81.
5.2 Maximum limitation of boiler temperature
(TKmax)
No damage to the boiler resulting from condensation.
The boiler temperature limitations are protective functions for the boiler.
Setting range
Unit
Factory setting
TKmin...120
°C
80
Tkmin
Minimum limitation of boiler temperature (setting on line 81)
The setting will change the boiler temperature’s maximum limitation.
If the boiler temperature reaches the level set here, the burner will be switched off.
20
10
0
-10
-20
40
30
60
50
80
70
TK
TK
TK
TK
SDK
2371Z26
TA
°C
° C
w
min
max
gem
0
Legend
T K
Boiler temperature
TKw
Boiler temperature setpoint
Tkmin
Minimum limitation of boiler
temperature
SDK
Switching differential
TAgem
Composite outside temperature
Benefit
Setting
Effect
Benefit
Description
Setting
Effect