129/218
Siemens Building Technologies
Basic Documentation RVA63.242, RVA53.242
CE1P2373E
Landis & Staefa Division
Description of heating engineer settings
26.03.2001
4.63 LPB segment address
The segment address and the device address are used as destinations in the bus
system. To ensure communication, each device must be correctly addressed.
Setting range
Unit
Factory setting
0...14
Increment
0
Entry of the segment address is especially important when used in a system. With this
setting, the system can be subdivided into a number of segments.
0
Heat generation segment
1...14
Heat consumer segment
A bus segment is comprised of a number of devices that are used in the same place of
application. All devices in a segment must carry the same segment address.
Addressing is part of engineering. For detailed information, refer to LPB System
Engineering, Basic Documentation (reference number CE1P2370E).
4.64 LPB power supply
A central bus power supply is not required in systems with up to 16 devices.
Straightforward extension of systems.
The controller ensures a direct power supply to the bus system.
Setting range
Unit
Factory setting
0 / 1
Increment
1
Entry:
0
Off: No power supply from the controller to the bus
1
Automatically: The power supply from the controller to the bus will automatically
be switched on and off, depending on the requirements of the LPB
The actual status of the power supply is shown on line 143.
Depending on the design of the system, the bus is powered either via the connected
devices or by a central bus power supply.
The design of the bus system is part of engineering. For detailed information, refer to
LPB System Engineering, Basic Documentation (reference number CE1P2370E).
Description
Setting
Effect
Segment number
Note
Benefits
Description
Setting
Effect
Note
Bus power supply
Note