170/218
Siemens Building Technologies
Basic Documentation RVA63.242, RVA53.242
CE1P2373E
Landis & Staefa Division
Description of OEM settings
26.03.2001
5.22 Gain factor of room influence (KORR)
The influence of room temperature deviations on the controlled system can be
adjusted.
Room influence can be activated and deactivated (setting on line 101).
Setting range
Unit
Factory setting
0...20
–
4
This setting will change the authority of the room temperature influence.
Increase:
Authority of room influence will increase
Decrease:
Authority of room influence will decrease
One half of the setting made on line 31
OEM
is multiplied by the deviation of the room
temperature setpoint from the actual value.
The result is then added to the room temperature setpoint.
TRx)
-
(TRw
2
31
+
TRw
=
TRwk
OEM
TRw
Room temperature setpoint
TRx
Actual value of the room temperature
TRwk
Corrected room temperature setpoint
The gain factor of room influence is only active when a room unit is connected.
5.23 Constant for quick setback and optimum start
control (KON)
Making use of the building’s thermal storage capacity.
Quick setback is dependent on whether or not a room sensor is used. Therefore, we
speak of quick setback with or without room influence.
This setting is active only if
no
room sensor is used.
Setting range
Unit
Factory setting
0...20
–
2
The duration of quick setback and the forward shift will be changed.
Entry:
Increase:
Longer setback and forward shift times.
For heavy and well insulated buildings that cool down slowly and that
require longer heating up times.
Decrease:
Shorter setback and forward shift times.
For light and poorly insulated buildings that cool down quickly and that
require shorter heating up times.
Benefit
Note
Setting
Effect
Correction
Note
Benefit
Description
Important
Setting
Effect