122/218
Siemens Building Technologies
Basic Documentation RVA63.242, RVA53.242
CE1P2373E
Landis & Staefa Division
Description of heating engineer settings
26.03.2001
4.56.3 Temperature-time integral
This temperature-time integral generates the locking signal for restricting the heating
circuits.
Diagram
Procedure
a to b
Within a foreseeable period of time, the actual boiler temperature (TKx)
will
not
lie within half the switching differential of the boiler temperature
setpoint.
è
Locking signal will be built up
b to c,
d to e
Within a foreseeable period of time, the actual boiler temperature (TKx)
will lie within half the switching differential of the boiler temperature
setpoint.
è
Locking signal will remain at a constant level
c to d,
e to f
Within a foreseeable period of time, the actual boiler temperature (TKx)
will lie
above
TKw.
è
Locking signal will be decreased
f
The actual boiler temperature (TKx)
exceeds
the boiler temperature
setpoint.
è
Locking signal will be set to 0 %.
TKx
2378Z11
t
a
b
TK
TKw
0%
t
y
x%
c
d
e
f
SDK/2
a
Start of d.h.w. heating
T K
boiler temperature
TKw
Boiler temperature setpoint
TKx
Actual value of the boiler temperature
SDK
Switching differential of the boiler
t
Time
Y
Locking signal
Diagram