Landis & Staefa Division
Description of OEM settings
26.03.2001
5.23.1 Quick setback without room influence
Quick setback is started as soon as a change to a lower room temperature setpoint
takes place (e.g. switching times in automatic mode).
The heating circuit pump will be deactivated until the quick setback time has elapsed,
which is generated from setting 32
OEM
, the composite outside temperature and the
room temperature setpoint change.
The example applies to a setpoint step change of 4 °C (e.g. TRw from 20 to 16 °C):
Setting on line 32
OEM
TAgem
0
4
8
12
15
20
- 20
0
0
0
0
0
0
- 10
0
0.5
1
1.5
2
2.5
0
0
3
6
9
11
15
+10
0
5
11
15 (16.5)
15 (21)
15 (27)
Values in hours
If a room sensor is connected, the quick setback time will not be generated from this
setting. Also refer to
“quick setback with room temperature influence”
in Index.
5.23.2 Optimum start control without influence
Also refer to "optimum start control" in Index.
Example