172/218
Siemens Building Technologies
Basic Documentation RVA63.242, RVA53.242
CE1P2373E
Landis & Staefa Division
Description of OEM settings
26.03.2001
5.24 Boost of room temperature setpoint (DTRSA)
Reduction of the building’s heating up time.
This setting is active only if a room sensor is used.
Setting range
Unit
Factory setting
0...20
°C (K)
5
The duration of boost heating will be changed.
Entry:
Increase:
More setpoint boost
Heating up time will become shorter
Decrease:
Less setpoint boost
Heating up time will become longer
5.24.1 Boost heating
Boost heating is started as soon as switching to a higher room temperature setpoint
occurs (e.g. switching times in automatic mode).
With the setting on line 33
OEM
, the room temperature setpoint will be raised until the
room is heated up (TRw - ¼ °C).
The boost produces an increase in the flow temperature setpoint.
20
15
°C
t
TR
w
TR
x
2371D03
a
b
TRx
Actual value of the room temperature
TRw
Room temperature setpoint
33
OEM
Setpoint boost
t
Time
Benefit
Note
Setting
Effect