7ML19981BC01
99
InterRanger
DPS300
If Peripheral Communications (P740) is set for “formatted” messages, a comma is
inserted between each message field (except immediately preceding the “End of
Message” characters).
MT-00 Measurement Message
Field Name
Definition
Start Of Message
STX ($02)
Message Type
2 characters, 00 (indicates the following data pertains to a
scan point measurement)
Point #
3 characters, 001 to 003 (e.g. the message pertains to Point
Number 1)
Reading
5 characters, 0.000 to 9999. (e.g. reading = 678.9, DDDD. =
no data, EEEE. = overflow)
Status A
1 character, $0 to $F (convert to binary, e.g. temp, echo, and cable OK, not
priority)
MSB LSB
####
1
=
temp
alarm
1 = loss of echo (failsafe expired)
1 = transducer cable fault
1
=
priority
point
Status B
1 character, $0 to $F (convert to binary, e.g. scan point is in high alarm)
MSB LSB
####
1 = low low alarm
1 = low alarm
1 = high alarm
1
=
high
high
alarm
Start of Message
Point #
Status A
Status C
Percent
End of Message
Temperature
Status B
Reading
Message type