7ML19981BC01
85
InterRanger
DPS300
P818 (V) Profile Pointer Distance
Observe the distance (in P005 Units) between the transducer face and the Profile
Pointer.
Values:
0.000 to 9999
P819 (V) Profile Pointer Amplitude
Observe the amplitude (in dB above 1 µV rms) of the Echo Profile at the Profile
Pointer position.
Values:
0 to 99
P820 Algorithm
Use this feature to select the
Algorithm(s)
(mathematical operations) on which the
Sonic Intelligence™ echo selection is based.
This value is automatically altered by Material (P002).
If the wrong echo is processed, select an alternate algorithm, while observing the
resultant echo processing displays.
To select an Algorithm...
1. Press to display the Auxiliary Function symbol,
2. Press or
to display the desired Reading display symbol(s),
3. Press (when the desired Algorithm is displayed)
Algorithms are characterized by a combination of echo characteristics:
area
= echo with most area above the TVT
largest
= echo with the largest amplitude above the TVT
first
= first echo above the TVT to be received
last
= last echo above the TVT to be received
Values:
ALF
= Area, Largest, and First average.
A =
Area
only.
L =
Largest
only
F
= First only
AL
= Area and Largest average
AF
= Area and First average
LF
= Largest and First average
bLF
= Largest or First
bL
= Largest only
bF
= First only
LASt
= last only (first echo from empty)