P663 Temperature Transducer Allocation
As preset, the temperature sensor inside of transducer number 1 and 2 are
allocated to Point Numbers 1 and 2 respectively. So, the temperature sensor of
transducer 1 is allocated to Point Number 1 and 2 is allocated to 2.
To alter this allocation, enter the transducer number whose temperature
measurement will be used for the distance calculation of the Point Number
displayed.
When both transducers are allocated to one Point Number, the temperature
measurements from each transducer are averaged for that clarifier.
Values:
1 = Transducer number 1
2 = Transducer number 2
1.2 = Transducer number 1 and 2 average
P664 (V) Temperature
View the current temperature in °C.
This is the value displayed when
is pressed in the RUN mode.
If Temp Source (P660) is set to any value other than Fixed Temp, the value
displayed is the temperature measured. If Temp Source is set to Fixed Temp, the
P661 value is displayed.
Values:
-50 to 150
Rate Parameters (P700 to P707)
P700 Max Fill Rate
Adjust the DPS300 response to increases in the actual sludge level (or advance to
a higher Failsafe Material Level, P071).
Note:
Enter a value slightly greater than the maximum clarifier filling rate.
The value is in Units (P005) or % of Span (P007) per minute.
Values:
0.000 to 9999
P701 Max Empty Rate
Adjust the DPS300 response to decreases in the actual sludge level (or advance
to a lower Failsafe Material Level, P071).
Note:
Enter a value slightly greater than the maximum clarifier emptying rate.
The value is in Units (P005) or % of Span (P007) per minute.
Values:
0.000
to
9999