InterRanger DPS300
46
7ML19981BC01
QUICK START PARAMETERS
Alter the Quick Start Parameters as required to suit the installation requirements.
Refer to the Application Example for assistance, if required.
Note:
When powered up, the DPS300 will take up to five minutes to lock onto its first
measurement. During this time several errors may be reported. These errors
should be ignored. If errors are reported after the five-minute startup period,
consult the Troubleshooting section.
P001 Operation
Enter the type of RUN mode operation desired.
Select:
“level”,
display Empty (P006) to sludge level distance.
“space”,
display Span (P007) to sludge level distance.
“distance”,
display transducer face to sludge level distance.
“out-of-service” the transducer is not scanned, alarm relay(s) energize, pump
relay(s) de-energize, and mA output(s) go to the Empty value.
Values:
0 = out-of-service
1 = level (preset)
2 = space
3 = distance
P002 Material
Enter a value for the type of clarifier being monitored.
The DPS300 will detect the sludge interface in a variety of applications. Select the
appropriate value from the list below for the DPS300 mounting and clarifier type
that most closely matches your application.
Note:
Several other parameter values are preset by P002. See DEFAULT
PARAMETER SETTINGS on page 106 for a complete list.
Demonstration
0 = For demonstration purposes in air only.
Primary Wastewater Clarifiers
1 = Stationary mounting with surface skimmers and bottom scrapers (preset).
2 = Stationary mounting with bottom scrapers only.
3 = Rectangular clarifier with travelling bridge arrangement.
4 = Circular clarifier with rotating bridge arrangement.