
7ML19981BC01
65
InterRanger
DPS300
P202 mA Allocation
Use this feature if Point Number to mA output allocation alteration is required.
Enter the Point Number(s) the mA output displayed, is to be based upon.
As preset, mA outputs 1 and 2 are allocated to Point Numbers 1 and 2
respectively.
If Point 1 and 2 are allocated to a single mA output, the output value represents
the Dual Point Average. (The Quick Start Parameter values should be identical for
both points).
When both mA outputs are allocated to the same Point Number, the mA Setpoint
parameters may be used to establish two separate or overlapping mA output
spans. However, the mA Value / Transducer (P203) corresponds to mA Output 1
only.
Values
:
1 = Point 1
2 = Point 2
1.2 = Dual Point Average
P203 (V) mA Value / Transducer
View the current value of the mA output associated with the Point Number
displayed.
This is the Auxiliary Reading displayed when [mA] is pressed in the RUN mode.
If both mA outputs are allocated to the same Point Number, the value of mA
Output 1 is displayed.
Values:
0.000 to 22.00
P210 0/4 mA Setpoint
Use this feature to reference the minimum mA output to any point in the
measurement range.
Enter the material level (referenced to Empty, P006) corresponding to the
minimum mA output.
This feature is preset to 0% or 100% of Span (P007) as determined by Operation
(P001).
Typically, this value is entered in Units (P005) or percent of Span (P007). If mA
Function is set for “volume”, enter the value in the Max Volume (P051) units or in
percent of Max Volume.
Values:
-999 to 9999
P211 20 mA Setpoint
Use this feature to reference the 20 mA output to any point in the measurement
range.
Enter the sludge level (referenced to Empty, P006) corresponding to 20 mA.