This feature is preset to 0% or 100% of Span (P007) as determined by Operation
(P001).
Typically, the value is entered in Units (P005) or percent of Span (P007). If mA
Function is set for “volume”, enter the value in the Max Volume (P051) units or as
a percent of Max Volume.
Values:
-999
to
9999
P212 mA Min Limit
Use this feature to prevent the mA output from falling below the minimum
acceptable mA input value (preset to 3.800 mA) of the device connected.
Values:
0.000 to 22.00
P213 mA Max Limit
Use this feature to prevent the mA output from exceeding the maximum
acceptable mA input value (preset to 20.20 mA) of the device connected.
Values:
0.000 to 22.00
P214 4 mA Trim
Use this feature (in combination with 20 mA Trim) if the device connected to the
mA output displayed is out of calibration, yet device recalibration is impractical.
Adjust this value (preset to 0.000) as required to make the device connected
indicate 4.000 mA when this parameter is accessed.
Values:
-1.00 to 1.000
P215 20 mA Trim
Use this feature (in combination with 4 mA Trim) if the device connected to the mA
output displayed is out of calibration, yet device recalibration is impractical.
Adjust this value (preset to 0.000) as required to make the device connected
indicate 20.00 mA when this parameter is accessed.
Values:
-1.00 to 1.000
P219 mA Failsafe
Use this feature if mA output failsafe operation, independent from the Failsafe
Material Level (P071) is desired.
To select an independent mA Failsafe option value:
1. Press to display the Auxiliary Function symbol,
2. Press or , to scroll access the failsafe options.
3. Press with the desired option displayed.