7ML19981BC01
51
InterRanger
DPS300
System Performance Evaluation
For initial RUN mode entry (or after any programming alteration), do not use the
DPS300 to operate process control equipment until satisfactory system
programming and performance is verified.
1. Press to enter the RUN mode.
“----” may be displayed briefly while the DPS300 takes measurements and
calculates the Reading.
If an alarm symbol is displayed, the corresponding relay is de-energized.
POINT #
ALARM INDICATOR
RELAY #
1 High
Alarm
1
1 Low
Alarm
2
2 High
Alarm
3
2 Low
Alarm
4
2. Press to display Readings in
%
(percent of Span, P007) based upon Operation
(P001).
OPERATION
LEVEL
SPACE, or DISTANCE*
Empty to Full =
0 to 100%
100 to 0%
* Objects close to the transducer face (0%) are not detectable.
3. Press to observe the mA output value for the Point Number displayed
(Auxiliary Reading).
OPERATION
LEVEL
SPACE, or DISTANCE*
Empty to Full =
4-20 mA
20-4 mA
* Objects close to the transducer face (4 mA) are not detectable.
4. Press to observe the
Failsafe Time Left
(time left in percent before failsafe
activation).
Each time a valid measurement is made for the Point Number displayed, this
value (Auxiliary Reading) is reset to 100 and begins to fall toward 0 until the next
valid measurement is made.
If the Failsafe Time Left reaches 0, the DPS300 flashes “LOE” in the Reading
display.
All associated data is supplied to the Peripheral Communications terminals (27
and 28). If a BIC-II is connected, refer to TECHNICAL REFERENCE /
Communication Support for message format and protocol information.