7ML19981BC01
55
InterRanger
DPS300
Reading Parameters (P060 to P062)
If Reading alteration is required, alter the following parameters to:
•
alter the number of decimal places displayed.
•
convert to units other than Units (P005), % of Span (P007), or Max Volume
(P051).
•
reference measurements to some point other than Empty (P006) or Span (P007).
Note:
If alteration is not required, proceed to FAILSAFE PARAMETERS.
P060 Decimal Position
Enter the maximum number of decimal places to be displayed in the Reading.
In the RUN mode, the number of decimal places displayed is automatically
adjusted (if necessary) to prevent the number of Reading digits from exceeding
display capabilities.
This value is automatically altered when Units (P005) or Max Volume (P051) are
altered.
Values:
0 = no digits after the decimal point
1 = 1 digit after the decimal point
2 = 2 digits after the decimal point
3 = 3 digits after the decimal point
P061 Convert Reading
Enter the value to multiply the Reading by, (before display).
This feature is preset to 1.000 (no conversion).
e.g.
If the Reading is currently displayed in feet, to display in yards, enter 3.
Note:
Avoid entering a value that, when multiplied by the maximum current Reading,
could exceed 5 digits before the Decimal Position.
Values:
-999 to 9999
P062 Offset Reading
Enter the value to be added to the Reading, (before display).
This feature is preset to 0.000, (no offset).
This feature affects the DPS300. Reading only. (Relays and mA outputs are not
affected).
Values:
-999 to 9999