7ML19981BC01
39
InterRanger
DPS300
Communication
Note
The communication protocol is automatically detected by the DPS300 and shown
via LED on the motherboard.
Serial: RS-232
RS-485
Bipolar Current
Connect the Milltronics BIC-II (if required) to the Peripheral Communications terminals
as below.
SmartLinx
Refer to the appropriate SmartLinx manual for installation and wiring information.
to customer device,
RS-232 port
15m (50 ft) max
to customer device,
RS-485 port
1200m (4,000 ft) max
Ground shield at
one end only.
Beldon 8760 (or equivalent), 18
AWG, 2 wire, shielded/twisted,
1500 (5000 ft) max.
refer to BIC-II instruction manual
to RS-232 or RS-422 host
device, 15 m (50 ft), or 1200m
(4,000 ft) max respectively.