7. In the
Volts Mode
screen, press
to go to the
PT/CT Setup
screen.
8. In the
PT/CT Setup
screen, press
to highlight the potential
transformer (PT) or current transformer (CT) value for editing. Press
to
edit the highlighted value.
NOTE:
If you have exceeded the password timeout period, you are
prompted to enter your meter’s display password.
9. Press
to change the value of the highlighted digit (0 - 9). Press
to go to
the next digit. Press
to enter the new value. When the confirmation
screen is displayed, press
to confirm the new value or
to revert to the
original value.
Related Topics
Display setup
You can configure basic display parameters using the display.
Screen setup
Parameter
Values
Description
Backlight
Timeout
0 to 720
Specifies how many seconds the display’s
backlight remains lit after the last button press
Label & symbol setup
Parameter
Values
Description
Phase Lbls
ABC, 123
Sets the voltage and current phase labels
Measurement
Symbols
IEEE, IEC
Specifies whether IEEE or IEC measurement
symbols are applied to displayed values
PF Convention
IEEE, IEC
Specifies whether IEEE or IEC power factor
conventions are applied to displayed values
108
7EN05-0390-00