Extended waveform capture
The meter’s Waveform Recorder modules support extended waveform capture.
The Waveform Recorder module’s
Pre-trigger Records
setup register specifies
how many pre-event records are saved with each triggered recording. The
Post-
trigger Records
setup register specifies how many post-event records are saved
with each triggered recording.
Both
Pre-trigger Records
and
Post-trigger Records
are set to zero by default. To
configure the waveform recorder for extended waveform capture, either or both of
these setup registers must be set to a non-zero positive integer value. If you do
this, you must also set the
Record Delay Cycles
setup register to zero in order to
properly configure the extended waveform capture.
A
Waveform recording triggered
B
Waveform record captured at trigger
C
Pre-trigger waveform records captured
D
Post-trigger waveform records captured
The waveform log set for each triggered recording is equal to the sum of
Pre-
trigger Records
+
Post-trigger Records
+ 1 (where 1 is the actual record when the
Waveform Recorder module’s
Record
input was triggered).
For example, if
Pre-trigger Records
is set to 2 and
Post-trigger Records
is set to 6,
the number of records for each waveform log set is 9:
7EN05-0390-00
155