2. Open the Setup Assistant for your meter.
3. Navigate to
Power Quality > Advanced PQ Logging
.
4. Select
4-30 Enable
and click
Edit
to configure your meter’s IEC 61000-4-30
logging parameters.
5. Configure the settings as required:
IEC 61000-4-30 Setup
Parameter
Description
Enabled
Select if you want to enable IEC 61000-4-30 monitoring.
NOTE:
This option must be enabled when monitoring EN 50160
or IEE 519 parameters.
Threshold
Specifies the percentage of nominal voltage that defines a
disturbance. For example, if you set this to 10% of 120 V nominal, the
disturbance occurs when the voltage dips to 12 V and below.
Hysteresis
Specifies the percentage above the Threshold that defines the end of
the disturbance. For example, if you set this to 2%, the end of the
disturbance occurs when the voltage rises to (10% + 2%) of nominal,
or 14.4 V and above.
Log 4-30 3s
measurements
Select if you want to enable IEC 61000-4-30 3-second interval data
logging.
Log 4-30 10s
measurements
Select if you want to enable IEC 61000-4-30 10-second interval data
logging.
6. Click
Send
to save your changes.
The
Advanced PQ Logging
screen shows the new configuration.
7. Select
EN 50160 enable
.
If you want to delete all logged EN 50160 data, click
Reset
, then click
Yes
to
confirm.
8. Click
Edit
to configure your meter’s EN 50160 logging parameters.
NOTE:
You must enable IEC 61000-4-30 before the meter can start
monitoring EN 50160 parameters.
9. Configure the settings as required:
EN50160 Configuration Setup
Parameter
Description
Enabled
Select if you want to enable EN 50160 monitoring.
Nominal Voltage
Specifies the nominal voltage value used for EN 50160.
Nominal Frequency
Specifies the nominal frequency used for EN 50160.
Log EN50160
measurements
Select if you want to log EN 50160 parameters. Note that you need to
enable EN 50160 monitoring in order to log the parameters.
10. Click
Send
to save your changes.
The
Advanced PQ Logging
screen shows the new configuration.
11. Select
519 enable
and click
Edit
to configure your meter’s IEEE 519 logging
parameters.
NOTE:
You must enable IEC 61000-4-30 before the meter can start
monitoring IEEE 519 parameters.
7EN05-0390-00
143