A
Waveform recording triggered
B
Waveform record captured at trigger
Delayed waveform capture
The meter’s Waveform Recorder modules support delayed waveform capture.
The Waveform Recorder module’s
Record Delay Cycles
setup register specifies
how many cycles to delay the waveform capture after the
Record
input is
triggered. This is for capturing post-trigger waveform data.
A
Waveform recording triggered
B
Waveform record if
Record Delay Cycles
was set to zero
C
Delay period (number of cycles specified in
Record Delay Cycles
setup register)
D
Delayed waveform capture recorded in waveform log
154
7EN05-0390-00