Ethernet loop topology
A. Ethernet switch or hub
B. Ethernet connected
meters
C. LAN / WAN
Protocols, ports and connections
The Ethernet protocols supported by your device allow simultaneous connections
through the IP service ports.
NOTE:
Some protocol port numbers are read-only and not configurable.
Protocol
Port (default)
Number of
connections
ION
7700
8
1
DNP
20000
DLMS
4059
Modbus TCP
3
502
Modbus RTU over Ethernet
3
7701
Modbus TCP (dedicated)
3
502
32
EtherGate (Com1)
7801
1
EtherGate (Com4)
7802
1
DHCP
67 (68)
1
FTP
21 (20)
2
Webserver (HTTP)
2
80
10
Secure webserver (HTTPS)
2
443
10
SNMP
161
N/A
SMTP server (email) outgoing only
25
1
NTP
123
1
IEC 61850
102
5
1
These 8 simultaneous connections are shared by ION, Modbus TCP, Modbus RTU over Ethernet,
DNP and DLMS. You can have a maximum of 3 DNP connections. You can have a maximum of 1
DLMS connection.
2
These are used for the meter’s webpages.
3
These protocols must be enabled for Modbus gateway functionality.
By enabling or disabling TCP/IP protocols, you can control whether or not your
meter accepts new socket connection requests. Changing settings for one port
does not impact the other existing connections. Depending on the protocol, you
can also change the port number.
7EN05-0390-00
27