5. Review the remote display firmware upgrade details stored in the meter’s
event log to confirm that the upload was successful.
Related Topics
Remote display troubleshooting icons
Accessing your meter’s FTP server
Loading option module firmware using ION Setup
You can upload firmware to your meter’s option modules using ION Setup over an
Ethernet connection.
You must perform the upload process separately for each type of module.
You must have:
•
Your meter’s Option Module firmware file (.S19). You can download upgrade
files from www.usa.siemens.com/pds.
•
The option module connected to your meter.
•
FTP access to your meter from the computer running ION Setup.
Your meter’s digital and analog outputs may change state during a firmware
upgrade. Option modules are offline during an option module firmware upgrade;
they will not communicate to the meter and the outputs may change state during
the upgrade process.
WARNING
UNINTENDED OPERATION
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Do not use this device for critical control or protection applications where human
or equipment safety relies on the operation of the control circuit.
NOTE:
If your meter’s option module loses power during firmware upload, the
option module will revert to its original firmware and you will have to reload the
firmware file.
1. Obtain the Option Module firmware files (.S19) that you want to load onto
your option module(s). Save the files where they can be accessed by the
computer running ION Setup.
2. Start ION Setup.
3. Open the Setup Assistant for your meter.
4. Select the
Template
screen.
5. Click the
Firmware Upgrade
tab, then click
Upgrade
. Enter your meter’s
password if prompted and click
OK
.
6. Navigate to where you have stored the option module firmware. Select the
Option Module firmware file (*.S19) as the file type.
7. Select the option module firmware file and click
Open
.
An ION Setup window will open. Click
Yes
to confirm the firmware upgrade.
8. The Option Card Upgrade window opens. Select the Slot that corresponds to
the Option Module type. You can select multiple slots for the same option
module type.