Disturbance direction detection events
The results of the disturbance direction detection algorithm appear in the meter’s
event log.
The image below shows an example of how the Disturbance Direction Detection
event appears in your meter’s event log when viewed using ION Setup.
NOTE:
You can view your meter’s event log throughION Setup, the meter
webpages or display.
See the
ION Reference
, available from www.usa.siemens.com/pds, for more
detailed information about the Disturbance Direction Detection module.
Related Topics
COMTRADE
Your meter can generate COMTRADE files and store them on the meter’s internal
FTP site.
COMTRADE stands for COMmon format for TRAnsient Data Exchange defined
by IEC 60255-24, and defines a common format for power quality event
(disturbance) data in order to simplify retrieval, analysis and exchange of
disturbance data between multiple sources and vendors.
The format of your meter’s COMTRADE files is as defined by IEC 60255-24.
COMTRADE can be used in conjunction with IEC 61850.
See the
COMTRADE and ION technology
technical note, available from
www.usa.siemens.com/pds, for detailed information about COMTRADE file
formats and implementation.
Related Topics
COMTRADE implementation overview
COMTRADE is configured as part of the default waveform recording framework.
COMTRADE records are generated for sag/swell events. Configure your meter
nominal voltages to enable waveform recording. COMTRADE records are stored
as read-only files on your meter’s internal FTP server, and are deleted when you
perform a Master reset of the meter, upgrade firmware or make changes to the
waveform recorders.
By default:
•
The meter is configured so COMTRADE records are generated for the default
waveform recorders.
NOTE:
If you add additional waveform recorders and you want
COMTRADE files generated for these new recorders, you need to
configure a new COMTRADE module using ION Setup Advanced mode.
You can configure up to three COMTRADE modules.
•
The oldest COMTRADE record is overwritten by the newest record when the
COMTRADE depth is exceeded.
7EN05-0390-00
149