4. Configure your meter’s SNMP parameters by selecting the parameter and
clicking
Edit
. Click
OK
in the editing screen to set the parameter value.
Parameter
Description
Enable SNMP
Enables or disables SNMP on your meter.
Enable Traps
Enables or disables SNMP trapping on your meter.
Trap Rcvr Addr1 —
Trap Recvr Add4
Enter up to four trap receiver IP addresses where trap messages will
be sent.
Read only
community
Enter the community string used for SNMP get (read-only) requests.
Read write
community
Enter the community string used for SNMP set (read/write) requests.
NOTE:
You can use the read/write community string for SNMP
get (read-only) requests.
System contact
Enter the name of your SNMP system administrator.
System name
Enter a descriptive name for your meter.
System location
Enter your meter’s location.
5. Review the rest of the SNMP information and modify if necessary.
Configuring SNMP using your meter’s webpages
You can configure SNMP trapping using your meter’s webpages.
You must download the ION MIB file from www.usa.siemens.com/pds.
1. Connect to your meter’s webpages.
2. Go to
Setup
>
SNMP Parameters
.
3. Configure your meter’s SNMP parameters by selecting the parameter value.
Parameter
Range
Description
Enable SNMP .
Yes/no
Enables or disables SNMP on your meter.
SNMP Port Number
161 (default)
Enter your meter’s SNMP port number.
System contact
—
Enter the name of your SNMP system administrator.
System name
—
Enter a descriptive name for your meter.
System location
—
Enter your meter’s location.
Read-only Community Name
—
Enter the community string used for SNMP get (read-only) requests.
Read-write Community Name
—
Enter the community string used for SNMP set (read/write) requests.
NOTE: You can use the read/write community string for SNMP get (read-
only) requests.
Enable SNMP Traps
Enable/disable
Enables or disables SNMP trapping on your meter.
Enable High Priority Alarms
Yes/no
Enables trapping of events that create high priority alarms.
Enable Med Priority Alarms
Yes/no
Enables trapping of events that create medium priority alarms.
Enable Low Priority Alarms
Yes/no
Enables trapping of events that create low priority alarms.
Report Buffer Size
1 - 30
Enter the maximum number of trap messages to be stored before the trap
messages are sent. Traps are sent when the number of trap messages is
equal to or greater than this value.
Report Hold Time
1 - 300 seconds
Enter the maximum duration for trap messages to be held. Trap
messages are sent when the time after a trap event has occurred is equal
to or greater than this value.
Trap Rcvr1 Addr -
Trap Rcvr4 Addr
—
Enter up to four trap receiver IP addresses, where trap messages will be
sent.
4. Click
Apply
to configure the meter’s SNMP parameters.