8. In the
Modbus Slave Map Setup
screen you can click
Delete
to remove a
Modbus register,
Set Name
to create a new name for the set of additional
data mapped to Modbus, or
Save As
to save the additional data you have
mapped to Modbus as a separate file.
9. Click
Finish
to complete your meter’s Modbus slave configuration and return
to the Setup Assistant.
Ethernet gateway
Ethernet gateway is a communications method that allows you to communicate
through a gateway device to a serial network.
When a meter with gateway capabilities is installed on an Ethernet network, a
master device (such as an energy management system) can communicate
through the gateway meter to a serial network of devices connected to the
gateway meter’s serial port(s). The maximum number of devices on the serial
network is determined by the limitations of the gateway meter’s serial port.
RS-485
120 Ω
A. LAN / WAN
B. Ethernet gateway meter
C. Serial RS-485 network of devices
D. Terminating resistor
There are two types of Ethernet gateways that you can configure on your meter:
•
EtherGate: a single TCP connection communicates through the gateway
meter to a serial network of devices.
•
Modbus gateway: up to a maximum of 32 Modbus master TCP connections
communicate through the gateway meter to a serial network of Modbus
devices.
EtherGate
The meter can function as an Ethernet gateway (EtherGate).
EtherGate is a protocol-agnostic communications method that lets you
communicate through a gateway meter to a serial network of devices letting ION
or other RTU over TCP data pass through the gateway meter to other networks,
including third party systems. When a meter installed on the Ethernet network has
EtherGate enabled, a master device (such as an energy management system)
can communicate through the gateway meter to a serial network of devices wired
to the gateway meter’s COM port. You must create an additional communications
connection to the gateway meter in order to read its information.
NOTE:
EtherGate supports only one master device.
Before proceeding, make sure you have completed the following tasks:
54
7EN05-0390-00