Load Cable Selection Tables
(Ex.) If used voltage is 120 V and voltage drops by 6 V.
Single-phase Cabtyre cables
(Unit: AWG)
Length
200 ft. (61 m)
or less
300 ft. (91 m)
400 ft. (122 m)
Current
10 A
10
8
8
20 A
8
6
4
30 A
6
4
2
50 A
4
2
1/0
100 A
1
2/0
3/0
130 A
1/0
3/0
4/0
7-2. Connecting Load Cables
< Note >
When connecting a load, check that the generator output setting, output terminal connection
position, and load power source are all matching.
If using the N/G terminal, be careful that the currents of each phase are uniform.
Use proper tools when connecting a load to sufficiently tighten the connection. Failure to
sufficiently tightened will result in cable burnout.
Terminal cover must remain closed during operation or breaker will trip.
(1) Single-Phase Three-Wire Output Terminal and Receptacle
For single-phase three-wire type load:
U-W terminal voltage is 240 V.
U-N/G terminal voltage is 120 V.
W-N/G terminal voltage is 120 V.
For single-phase 240 V load:
For single-phase 120 V load:
WARNING : ELECTRIC SHOCK
Always turn the breaker OFF, place the power switch in the OFF position and stop
the engine before connecting/disconnecting the load cable to the output terminal.
Close the output terminal cover before operating.
Do not insert a pin, needle or other metal object into the receptacle.
Do not touch the generator if the generator or casing becomes wet during operation.
CAUTION : FIRE
Do not connect the generator output to indoor wiring.