146
SDH Series Manual
PF82
(■)
PRCM
Pr command trigger register
Pr
0
0~~1000
-
Write 0, start to home return.
Write 1 ~ 63, start to operate assigned PR program which equal to DI
:
CTRG+POSn.
Write 64 ~ 9999, writing prohibition.
(
Value out of normal range
)
Write 1000, operate stop which equal to DI
:
STOP.
While Reading
:
If the command does not complete, then read the original command.
If the command has completed, then read the original c10000.
If the command has been completed and the DO: TPOS ON motor position reached then read the
original c20000.
For example
:
Write positioning command 3, trigger the PR program 3.
Read 3, that 3 execution of a program is not completed;
If 10003 is read as the program 3 command sent, but unfinished motor positioning;
If 20003 is read, as the program 3 command sent, and motor positioning is complete.
No
Abbr.
Function description
Control Mode
Initial Value
Setting range
unit
PF83
EVON
Upper edge-triggered PR program number
Pr
0000h
0000h~DDDDh
-
Parameter function
:
4 bit
:
UZYX
Set EVx is ON, operate PR number.
X=0
:
When EV1 is ON, do nothing.
X=1~D
:
When EV1 is ON, operate PR No.51~63
Y=0
:
When EV2 is ON, do nothing.
Y=1~D
:
When EV2 is ON, operate PR No.51~63
Z=0
:
When EV3 is ON, do nothing.
Z=1~D
:
When EV3 is ON, operate PR No.51~63
U=0
:
When EV4 is ON, do nothing.
U=1~D
:
When EV4 is ON, operate PR No.51~63
PF84
EVOF
Low edge-triggered PR program number
Pr
0000h
0000h~DDDDh
-
Parameter function
:
4 bit
:
UZYX
Set EVx is ON, operate PR number.
X=0
:
When EV1 is OFF, do nothing.
X=1~D
:
When EV1 is OFF, operate PR No.51~63
Y=0
:
When EV2 is OFF, do nothing.
Y=1~D
:
When EV2 is OFF, operate PR No.51~63
Z=0
:
When EV3 is OFF, do nothing.
Z=1~D
:
When EV3 is OFF, operate PR No.51~63
U=0
:
When EV4 is OFF, do nothing.
U=1~D
:
When EV4 is OFF, operate PR No.51~63
PF85
(■)
PMEM
PATH#1 ~ PATH#2 data is not memorized
settings when power off.
Parameter function
:
4 bit
:
00YX
X=0
:
PATH#1 data is memorized settings
when power off.
X=1
:
PATH#1 data is not memorized settings
when power off.
Y=0
:
PATH#2 data is memorized settings
when power off.
Y=1
:
PATH#2 data is not memorized settings
when power off.
Remaining reserves.
This parameter provides users to constantly
write new goal points through communication.
Pr.Pt
S.T
0000h
0000h
~
0011h
-
PF86
SWLP
Soft limit :forward
When Motor moved forward and feedback
the position that over the setting value of this
parameter would trigger alarm code AL14 in
PR mode.
Pr
2
31
-1
−2
31
+1
~
2
31
-1
pulse
PF87
SWLN
Soft limit :reverse
When Motor moved reverse and feedback
the position that over the setting value of this
parameter would trigger alarm code AL15 in
PR mode.
Pr
2
31
-1
−2
31
+1
~
2
31
-1
pulse
PF88
~
PF99
Reserved
Содержание SDH Series
Страница 1: ...SDH Series Manual ...
Страница 2: ......
Страница 22: ...13 Chapter 3 100W 1kW Shihlin servo driver Power source 100W 15KW 3Φ200 230Vac ...
Страница 190: ...181 Chapter 12 12 5 Dimensions of low inertia motor SMH L010 SMH L020 L040 SMH L075 ...
Страница 196: ...187 Chapter 13 As load torque is 300 operating time is 2 23S As load torque is 300 operating time is 2 28S ...
Страница 219: ......
Страница 220: ...2016 ...