86
Operating Instructions – MOVIDRIVE® MDR60A/61B
8
Error messages and list of errors
Service (MDR60A0150/0370/0750 and MDR61B1600/2500)
Error list
Error
Suberror
Code Designation
Response
(P)
Code
Designation
Possible cause
Measure
00
No error
01
Overcurrent
Immediate
disconnec-
tion
1
VCE monitoring or under-
voltage monitoring of the
unit driver
•
Short circuit at the power
input
•
regenerative power rating
too high
•
Defective output stage
•
Power supply
Current converter
•
Defective phase module
•
Supply voltage 24 V or 24 V
generated from it is instable
•
Interruption or short circuit
on the signal lines from the
phase modules
•
Rectify the short circuit
•
Limit regenerative power
rating; e.g. extend ramp
times of the motor inverter
•
Contact SEW Service for
advice if the output stage
is defective.
6
UCE monitoring or under-
voltage monitoring of gate
driver or overcurrent of
current converter
..Phase U
7
..Phase V
8
..Phase W
9
..Phases U and V
10
..Phases U and W
11
..Phases V and W
12
..Phases U and V and W
13
Voltage supply
Current converter in mains
operation
14
MFE signal lines defective Defective output stage
03
Ground fault
Immediate
disconnec-
tion
0
Ground fault
Ground fault
•
in the supply cable
•
in the regenerative power
supply
•
Eliminate ground fault
•
Consult SEW Service
1
Ground fault or current
converter error
•
Ground fault
–
in the supply cable
–
in the regenerative
power supply
•
defective current converter
•
Defective cable between
phase module and current
converter
•
Eliminate ground fault
•
Consult SEW Service
06
Line phase
failure
Immediate
disconnec-
tion (+ open
line contac-
tor)
0
DC link voltage periodi-
cally too low
•
Phase failure
•
Inadequate line voltage
quality
•
Check the line cable
•
Check configuration of the
supply system.
•
Check supply (fuses, con-
tactor)
3
Mains voltage failure
4
Line frequency fault
07
DC link
Immediate
disconnec-
tion
0
DC link voltage too high
DC link voltage too high
•
Extend deceleration ramps
of the motor inverter
•
Check braking resistor
supply cable (if available)
•
Check technical data of
braking resistor (if avail-
able)
•
Check configuration of the
supply system.
•
For supply voltages > 480
V, set the "Enable" and
"Controller inhibit" signals
simultaneously
Immediate
disconnec-
tion
(+ open line
contactor)
5
DC link undervoltage
DC link voltage too low
Immediate
disconnec-
tion
6
DC link voltage too high..
Phase U
DC link voltage too high
7
.. Phase V
8
.. Phase W
Immediate
disconnec-
tion
(+ open line
contactor)
9
DC link voltage
(Software detection)
09
Startup
Immediate
disconnec-
tion
(+ open line
contactor)
0
Startup missing
The regenerative power supply
has not been started up in the
hardware configuration yet.
Restore the factory settings in
the setup or load matching
data set.