Operating Instructions – MOVIDRIVE® MDR60A/61B
111
12
Electrical connection
Installation (MDR60A1320-503-00)
1. The relay picks up
– when the supply voltage is present;
– when the precharging of the DC link capacitors is complete
– when there is no group fault;
2. The relay drops out
• in case of an OFF command via terminals 7 and 8;
• in the event of an error message
3. Autostart does not require activation of the ON switch Observe chapter "Configura-
tion" (page 117).
12.3.5 Terminal assignment inhibit input A1/A2
terminal
Function
Description
X2:1 Normally
closed contact
Isolated relay contacts
1)
2)
Collective fault signal switching capability of the relay
contacts:
•
30 V DC3A
•
230 V AC5A
X2:2 Normally
closed contact
X2:3 Normally
open contact
X2:4 Normally
open contact
X2:5
Internally assigned to tempera-
ture monitoring
X2:6
X2:7
OFF switch
To switch off the regenerative power supply
X2:8
X2:9
ON switch / reset
3)
X2:10
X2:11 (+24 V)
External voltage input
To switch on the regenerative supply or confirm
errors
X2:12 (0 V)
terminal
Function
Description
A1
Inhibit input 24 V
Control voltage to inhibit the regenerative power sup-
ply path
A2
DGND
4066532107
Higher-level
Controller
Binary output
MOVIDRIVE
MDR60A1320
®
DGND
A1
A2