Operating Instructions – MOVIDRIVE® MDR60A/61B
25
4
Installation notes
Installation (MDR60A0150/0370/0750 and MDR61B1600/2500)
4.1.10 EMC-compliant installation
• All cables except for the supply system lead must be
shielded
. As an alternative to
the shielding, the option HD.. (output choke) can be used for the motor cable to
achieve the emitted interference limit values. .
• When using shielded motor cables, e.g. prefabricated motor cables from SEW-EU-
RODRIVE, you must keep the
unshielded conductors between the shield and
connection terminal of the inverter as short as possible
.
• Apply the
shield by the shortest possible route and make sure it is grounded
over a wide area at both ends
. Ground one end of the shield using an interference
suppression capacitor (220 nF/50 V) to avoid ground loops. If using double-shielded
cables, ground the outer shield on the inverter end and the inner shield at the other
end.
2394134795
Shielded cables
1804841739
Correct shield connection using metal clamp (shield clamp) or cable gland
U
V
W
L1 L2 L3
L1 L2 L3
MOVIDRIVE
®
B
HD005
NF 600
U
V
W