Operating Instructions – MOVIDRIVE® MDR60A/61B
51
4
Optional scope of delivery for size 7
Installation (MDR60A0150/0370/0750 and MDR61B1600/2500)
4.7.7
DLZ11B DC link coupling
You can use the
DLZ11B DC link coupling
to connect 2 size 7 units side by side. The
DLZ11B DC link coupling is available in three different lengths:
• 100 mm (part number: 1 823 193 4)
• 200 mm (part number: 1 823 566 2)
• 300 mm (part number: 1 823 567 0)
Proceed as follows to connect 2 units side by side:
1. Depending on the DC link coupling, the units that you want to connect must be in-
stalled at ground level and 100 mm, 200 mm or 300 mm apart from each other.
2. Loosen the 4 screws of the upper cover and remove it.
3. Loosen the 4 screws of the lower cover and remove it.
4. Cut the opening in the side panel according to chapter "Side panel for DC link cou-
pling" (page 50).
5. Insert the DC link connections into the units.
• Insert the
100 mm DC link connection
vertically into the unit.
• Turn the 100 mm DC link connection in the unit by 90°.
• Insert the
200 mm and 300 mm DC link connection
into the one unit skewed up
to the stop.