Operating Instructions – MOVIDRIVE® MDR60A/61B
8
Error messages and list of errors
Service (MDR60A0150/0370/0750 and MDR61B1600/2500)
44
Unit utilization
Immediate
disconnec-
tion
0
Unit utilization error
•
Unit utilization (IxT value)
> 125%
•
Decrease power output
•
Extend ramps of the motor
inverter
•
If suggested actions not
possible, use larger regen-
erative power supply unit.
•
Reduce load
45
Initialization
Immediate
disconnec-
tion (+ open
line contac-
tor)
1
Offsets of the current mea-
surement outside the per-
mitted range
•
No parameters set for
EEPROM in power section,
or parameters set incor-
rectly.
•
Option card not in contact
with backplane bus.
•
Current measurement is
defective
•
Error in the processor
periphery
•
Restore factory settings
Consult SEW Service if
the error still cannot be
reset.
•
Insert the option card cor-
rectly.
47
System bus 1
timeout
No
response,
(display
only)(P)
0
Timeout system bus
CAN1
Error during communication via
system bus 1.
Check system bus connection.
80
RAM test
Immediate
disconnec-
tion
0
"RAM test" error
Internal unit fault, RAM defec-
tive.
Consult SEW Service.
94
Unit configu-
ration data
Immediate
disconnec-
tion
1
CRC checksum error
Inverter electronics disrupted,
possibly due to effect of EMC or
a defect.
Send unit in for repair.
11
Power section data CRC
checksum error
97
Copy error
Immediate
disconnec-
tion
1
Download of parameter
set to unit cancelled.
•
Memory card cannot be
written or read.
•
Error during data transmis-
sion
•
Repeat copying process
•
Restore default setting
(P802) and repeat copying
process
98
CRC error
Immediate
disconnec-
tion (+ open
line contac-
tor)
0
"CRC via internal flash"
error
Internal unit error, flash memory
defective.
Send unit in for repair.
107
Line compo-
nents
Immediate
disconnec-
tion (+ open
line contac-
tor)
1
Line contactor feedback
contact error
•
Defective main contactor
•
Supply cable missing
•
Output stage defective
•
Control cables defective
•
Check main contactor
•
Check control cables and
line connection
•
Check line filter connec-
tion
4
Internal line cables are
swapped
5
Missing line cable or faulty
branch of the output stage
6
Unable to perform self-test
due to controller inhibit.
124
Ambient con-
dition
Immediate
disconnec-
tion
1
Permitted ambient tem-
perature exceeded
Ambient temperature > 60 °C
Improve ventilation and cool-
ing conditions, improve air
supply in the control cabinet,
check filter mats.
Error
Suberror
Code Designation
Response
(P)
Code
Designation
Possible cause
Measure