26
Operating Instructions – MOVIDRIVE® MDR60A/61B
4
Installation notes
Installation (MDR60A0150/0370/0750 and MDR61B1600/2500)
• You can also use
earthed sheet-metal ducts or metal pipes
to
shield the cables
.
Route
the
power and signal cables
separately
.
• Ground the
inverter
and
all additional units to ensure high-frequency compati-
bility
(wide area, metal-on-metal contact between the unit housing and ground, e.g.
unpainted control cabinet mounting panel).
NF.. line filter
• With the NF.. line filter option, the MOVIDRIVE
®
MDR60A/61B regenerative power
supply unit size 2, 3, and 7 can meet the requirements of limit value class C2.
• Do not switch between the line filter and the MOVIDRIVE
®
MDX60A/61B regenera-
tive power supply unit.
• Install the
line filter close to the regenerative power supply unit
but outside the
minimum clearance for cooling.
• Keep the
length of the cable between the line filter and regenerative power sup-
ply unit to an absolute minimum
, and never more than 400 mm. Unshielded,
twisted cables are sufficient. Use unshielded cables for the supply system connec-
tion as well.
Interference emis-
sion category
Compliance with category C2 according to EN 61800-3 has been tested in a CE typical
drive system. SEW-EURODRIVE can provide detailed information on request.
INFORMATION
• MOVIDRIVE
®
B is a product with restricted availability in accordance with EN
61800-3. It may cause EMC interference. In this case, it is recommended for the
operator to take suitable measures.
• For detailed information on EMC compliant installation, refer to the publication
"Electromagnetic Compatibility in Drive Engineering" from SEW-EURODRIVE.
NOTICE
This product can cause high-frequency interferences in residential areas which can re-
quire measures for interference suppression.