30
Operating Instructions – MOVIDRIVE® MDR60A/61B
4
Information regarding UL
Installation (MDR60A0150/0370/0750 and MDR61B1600/2500)
4.2.4
Ambient temperature
The units are suitable for an ambient temperature of 40 °C, max. 60 °C with derated out-
put current.
MOVIDRIVE
®
MDR60A0150 – 0750: To determine the output current rating at higher
than 40 °C, the output current should be derated 3.0 % per °C between 40 °C and 60 °C.
MOVIDRIVE
®
MDR61B1600 – 2500: To determine output current rating at higher than
40 °C, the output current should be derated 2.5% per °C between 40 °C and 50 °C, and
3% per °C between 50 °C and 60 °C.
INFORMATION
• Use only tested units with a
limited output voltage
(U
max
= DC 30 V) and
limited
output current
(I
max
= 8 A) as an
external DC 24 V voltage source
.
•
UL certification does not apply to operation in voltage supply systems with a
non-grounded star point (IT systems).