8
Service
Fault/error table
Operating Instructions – MOVIMOT
®
flexible
205
Subfault: 10.7
Description: Calculation result of multiplication/division command too large
Response: Application stop + output stage inhibit
Cause
Measure
Calculation result of multiplication/division com-
mand exceeds 32 bits.
Check the program.
Failed to write calculation result of multiplication/
division command into result variable.
Check the program.
Subfault: 10.8
Description: Illegal connection
Response: Application stop + output stage inhibit
Cause
Measure
Index used in connect not allowed.
Check the program. The index used either does
not exist or is not permitted for access via pro-
cess data – see parameter list.
Subfault: 10.9
Description: CRC code
Response: Application stop + output stage inhibit
Cause
Measure
Wrong CRC checksum of code.
Load the program again. The program memory is
corrupt. Unauthorized write access to the pro-
gram memory.
Subfault: 10.10
Description: Setpoint cycle time not supported
Response: Application stop + output stage inhibit
Cause
Measure
Non-supported setpoint cycle time parameterized. Set the setpoint cycle time to the default value
1 ms.
Subfault: 10.11
Description: No application program loaded
Response: Output stage inhibit
Cause
Measure
No Data Flexibility application program loaded.
Load the program or disable Data Flexibility.
Subfault: 10.99
Description: Unknown error
Response: Application stop + output stage inhibit
Cause
Measure
Unknown Data Flexibility error.
Contact the SEW‑EURODRIVE Service.
29129451/EN – 12/2019